PT. SRIAYU MULTI KREASI

Jln. Hayam Wuruk No. 2-5

Gedung Harco Glodok Lantai 5 Blok A.42 - Jakarta Barat

PT. SRIAYU MULTI KREASI

Dwyer Series AQTIA Air Quality Test Kits


Detail Dwyer Series AQTIA Air Quality Test Kits

Series AQTIA Air Quality Test Instruments Kits

AQTIA Combines the UHH2 Universal Handheld with Compatible Probes

THE SERIES AQTIA AIR QUALITY TEST INSTRUMENTS combine the versatile Model UHH2 handheld base with various compatible probes and modules. The versatile combination provides a line of instruments capable of streamlining a technician’s everyday testing by combining all into one product and using Bluetooth SIG, Inc. wireless technology for ease of use.

Product Applications

    • Building commissioning
    • Building balancing
    • Testing HVAC equipment performance

Model

  • AQTIA-AP2
    Air Quality Test Instrument Kit with UHH2 base unit, AP2 wireless hot wire thermo-anemometer, and UHH-BTG wireless mobile gateway.
  • AQTIA-RP2
    Air Quality Test Instrument Kit with UHH2 base unit, RP2 wireless thermo-hygrometer, and UHH-BTG wireless mobile gateway.
  • AQTIA-VP2Air Quality Test Instrument Kit with UHH2 base unit, VP2 wireless vane thermo-anemometer, and UHH-BTG wireless mobile gateway.
  • AQTIA-WDPM-002
    Air Quality Test Instrument Kit with UHH2 base unit, WDPM wireless 2″ w.c. manometer, and UHH-BTG wireless mobile gateway.
  • AQTIA-WDPM-005
    Air Quality Test Instrument Kit with UHH2 base unit, WDPM wireless 5″ w.c. manometer, and UHH-BTG wireless mobile gateway.
  • AQTIA-WDPM-010
    Air Quality Test Instrument Kit with UHH2 base unit, WDPM wireless 10″ w.c. manometer, and UHH-BTG wireless mobile gateway.
  • AQTIA-WDPM-020
    Air Quality Test Instrument Kit with UHH2 base unit, WDPM wireless 20″ w.c. manometer, and UHH-BTG wireless mobile gateway.
  • AQTIA-WDPM-030
    Air Quality Test Instrument Kit with UHH2 base unit, WDPM wireless 30″ w.c. manometer, and UHH-BTG wireless mobile gateway.
  • AQTIA-WDPM-100
    Air Quality Test Instrument Kit with UHH2 base unit, WDPM wireless 100″ w.c. manometer, and UHH-BTG wireless mobile gateway.
  • AQTIA-WDPM-200
    Air Quality Test Instrument Kit with UHH2 base unit, WDPM wireless 200″ w.c. manometer, and UHH-BTG wireless mobile gateway.
  • AQTIA-WDPM-350
    Air Quality Test Instrument Kit with UHH2 base unit, WDPM wireless 350″ w.c. manometer, and UHH-BTG wireless mobile gateway.

Specifications :

UHH2 SPECIFICATIONS

  • Display:
    4.3″ QHD Gorilla glass, 960×540
  • Wireless Distance:
    50′ (15 m) or greater.
  • Response Time:
    1 s.
  • Temperature Limits:
    Operating: -4 to 140°F (-20 to 60°C); Storage: -40 to 176°F (-40 to 80°C).
  • Humidity Limits:
    5 to 95% RH.
  • Power Requirements:
    2000mAh lithium ion battery, installed functional, non-replaceable.
  • Memory:
    RAM 1G & ROM 4G.
  • Operating System:
    Android® 4.2.2.
  • CPU:
    MTK6589W Quad Core 1.2 GHz.
  • Enclosure Rating:
    IP68.
  • Weight:
    15.9 oz (450 g).
  • Agency Approvals:
    CE.

AP2 THERMO-ANEMOMETER PROBE SPECIFICATIONS

  • Service:
    Dry, clean air.
  • Temperature Limits:
    Process: -20 to 200°F (-29 to 93°C); Ambient: -20 to 140°F (-29 to 60°C); Battery Charging: 32 to 113°F (0 to 45°C).
  • Range:
    Air Velocity: 0 to 6000 FPM (0 to 30 m/s); Volumetric Air: 999,999 in selected flow units; Temperature: -40 to 212°F (-40 to 100°C).
  • Accuracy:
    Air Velocity: ±3% FS within temperature range of 40 to 90°F (4 to 32°C); Temperature: ±0.5°F (±0.28°C).
  • Response Time:
    1 s.
  • Probe Length:
    8″ (203 mm) insertion.
  • Power Requirements:
    3.7 V YT562447 Lithium ion battery, installed functional, user replaceable.
  • Maximum Wireless Distance:
    50′ (15 m).
  • Handle Enclosure:
    Thermoplastic elastomer over polycarbonate.
  • Supplied With:
    Wrist strap.
  • Weight:
    11.2 oz (331.22 g).
  • Agency Approvals:
    CE (not while charging), FCC compliant.

RP2 THERMO-HYGROMETER PROBE SPECIFICATIONS

  • Service:
    Clean air.
  • Temperature Limits:
    Process: -4 to 140°F (-20 to 60°C); Ambient: 5 to 125°F (-15 to 51°C); Battery Charging: 32 to 113°F (0 to 45°C).
  • Range:
    RH: 0 to 100% (non-condensing); Temperature: -22 to 140°F (-30 to 60°C).
  • Accuracy:
    RH: ±2% @ 25°C (10 to 90% RH); ±4% (0 to 10, 90 to 100% RH); Temperature: ±0.54°F @ 77°F (±0.3°C @ 25°C).

Have any Question or Comment?