Detail Hioki 3169 Clamp On Power Hitester :
Features
- Simultaneously measure demand and harmonic waveforms taht share the same voltage line over 4-circuits
- Data can be saved onto a PC card
- High-speed and continious processing to measure individual waveforms
- High-speed D/A output for analog graph recording (Model 3169-21)
Specifications :
- Measurement libe and number of circuits : Single-phase 2-wires (4 circuits), single-phase 3-wires (2 circuit), three phases 3 wires (2 or 1 circuit), and three phases 4 wires (1 circuit)
Note : 50 or 60 Hz, and that share the same voltage libe - Measurement items : Voltage, Current, active/reacctive/apparent power, Active/reactive power intergation, power factor, frequency, harmonic waveform value
- Measurement range : [Voltage] 150.00 V to 600.00 V AC, 3 ranges, [Current] 500.00 mA to 5.0000 kA AC (depends on current sensor in use), [Power] 75.000 W to 900.00 kW (depends on combination of voltage, current range, and measurement line)
- Basic Accuracy :
AC Voltage : ±0.2% rdg. ±0.1% f.s
AC Current : ±0.2% rdg. ±0.1% f.s + current sensor accuracy
Active power : ±0.2% rdg. ±0.1% f.s + current sensor accuracy (at power factor = 1)
Clamp on sensor 9661 : ±0.3% rdg. ±0.1% f.s (different each sensor models) - Measurement method : Digital sampling, PLL synchronization or 50/60 Hz fixed clock
- Display refresh rate : 2 times/sec (except when a PC card accessing, or RS232 communications)
- Data save interval : Standard interval : 1 sec to 30 sec, 1 minute to 60 minutes, 13 selects
Fast interval : A single waveform, or 0.1, 0.2, or 0.5 sec (at instant value only) - Frequency characteristics : Fundamental waveforms up to the 50th order ±0.3% f.s + measurement accuracy (of a 45 to 66 Hz funcamental waveform)
- Other functions : Error connect check, language selection, display hold, setting backup, power shut off management, key lock, [3169-21 on;y] D/A output 4 channels, ±5 V DC f.s
- Power supply : 100 to 240 V AC, 50/60 Hz, 30 VA max
- Dimensions and mass : 210x160x60 mm , 1.2 kg