Detail KYORITSU 5410
Measurement of RCD trip time – Measurement of trip out current
Range
×5
×1
×1/2
AUTO RAMP (mA)
Rated Voltage
100V±10%
200V+32%/-10%
400V±10%
(50/60Hz)
Test current
15/30/50/100mA
15/30/50/100/200/500mA
15/30/50/100/200/500mA
Measuring range
Testing time
200ms
Testing time
2000ms
Testing time
2000ms
40% – 110% of lΔn
(goes up by 5%)
Testing time
300ms × 15steps
Accuracy
(Trip Time)
|±1%rdg±3dgt
|±1%rdg±3dgt
|±1%rdg±3dgt
Test Current
at each step
-4% – +4%
Accuracy
(Test Current)
|+2% – +8%dgt
|+2% – +8%dgt
|-8% – -2%dgt
Voltage Measurement
Measuring range
80V – 450V (50/60Hz)
Accuracy
|±2%rdg±4dgt
Applicable Standard
IEC 61010-1 Pollution degree2 CAT III 300V / CAT II 400V
IEC 61010-031
IEC 61557-1, 6
IEC 60529 (IP54)
Display
1999 counts (3 1/2digits), Large LCD
Operating temperature & humidity
0ºC – 40ºC, relative humidity 85% (no condensation)
Storage temperature & humidity
-20ºC – 60ºC, relative humidity 85% (no condensation)
Withstand Voltage
AC3700V / 1 min. (between electrical circuit and enclosure)
Insulation resistance
50MΩ or more / 1000V (between electrical circuit and enclosure)
Sleep Function
(1)
Automatically enters Sleep mode in 3 minutes after the last switch operation (current consumption 75µA). This function doesn’t work at voltage measurements. To exit from the Sleep mode, set the Function switch to OFF position once, and re-set it to the Range at which a measurement to be conducted.
(2)
Backlight turns off in 1 minute after it lights up.
Power Source
DC 12V / Size AA battery R6 (SUM-3) × 8 pcs.
Dimension
186(L)×167(W)×89(D)mm
Weight
Approx. 965g (including batteries)
Possible number of Measurements
1200 times or more
(measure every 30 seconds at ×1/2 Range, lΔn=100mA)
Accessories
7128A (Test leads)
7129A (Test lead with alligator clip)
8017 (Long pin) × 2
Cord case, Strap belt, Instruction manual,
Size AA battery R6 (SUM-3) × 8pcs.