Allows you to measure insulation resistance more safely by avoiding operation mistakes.
- Hot-line state (30V minimun) detection
- Large volt mark with buzzer sound
- Automatic data hold function
- Baragraph just like analog meter
- Large display with backlight
- Easy to use & tough body
- Display : numeral display 4000
- Sampling rate : 2 times/sec.
MG500 | Measuring Range | Best Accuracy | Resolution |
M Ω | 4M/40M/400M/4000M | ± (3%+4) | 0.001M Ω |
Test Voltage | 1000/500/250V | ||
ACV/DCV | 600V (AC/DC Automatic detection) | ± (3%+2) | 1V |
Ω | 4000Ω (Buzzer and alarm indicator) | ± (3%+3) | 1Ω |
Ω | 40Ω | ± (3%+10) | 0.01Ω |
Open circuit voltage | 1 to 1.3 times of nominal test voltage | ||
Rated Current | 1.0-1.2mA | ||
Short-circuit current | 2mA or less | ||
Live circuit detection | At ≥30V AC/DC or more, inhibits test, buzzer sounds and ALARM indicator lights up | ||
Battery | LR6 X 6 | ||
Size/Mass | H170x W142x D57mm /approx.600g | ||
Standard Accessories included | Test Lead (TL-112a), Strap (ST-50), Instruction manual |